| Type | SizeConn. O.D.S | DIA A | B | C | D | H | VOLUME(V) | CE Cat. | |
| mm | inch | ||||||||
| RA-S05-CE | 15.9 | 5/8" | 3.15 | 10.24 | 1.18 | 1.38 | 3/8-16 UNF | 1.0 | SEP |
| RA-S06-CE | 19 | 3/4" | 12.20 | 1.18 | 1.38 | 3/8-16 UNF | 1.1 | ||
| RA-204-CE | 12.7 | 1/2" | 4.00 | 8.47 | 1.18 | 2.12 | 3/8-16 UNF | 1.5 | |
| RA-205-CE | 15.9 | 5/8" | 10.83 | 1.38 | 2.12 | 3/8-16 UNF | 2.0 | Ⅰ | |
| RA-206-CE | 19 | 3/4" | 5.50 | 10.24 | 1.38 | 3.00 | 1/2-13 UNF | 3.6 | |
| RA-207-CE | 22.2 | 7/8" | 12.60 | 1.38 | 3.00 | 1/2-13 UNF | 4.4 | ||
| RA-211-CE | 28.5 | 1 1/8" | 6.50 | 15.75 | 1.77 | 3.20 | 1/2-13 UNF | 7.9 | Ⅱ |
| RA-213-CE | 34.9 | 1 3/8" | 20.87 | 1.77 | 3.20 | 1/2-13 UNF | 10.5 | ||
| RA-215-CE | 41.2 | 1 5/8" | 22.84 | 1.77 | 3.20 | 1/2-13 UNF | 11.5 | ||
| Max . Permissiblepressure: 31.03 bar(450psi) /-10°C~+150°C , 20.67 bar(300psi) / -45°C~-10°C | |||||||||
| RA-221-CE | 53.9 | 2 1/8" | 8.50 | 29.53 | 2.17 | 5.12 | 25.1 | ||
| RA-225-CE | 66.7 | 2 5/8" | 10.75 | 25.60 | 2.37 | 6.30 | 34.6 | Ⅲ | |
| RA-231-CE | 79.4 | 3 1/8" | 12.75 | 23.62 | 2.37 | 7.09 | 45.6 | ||
| RA-1831-CE | 79.4 | 3 1/8" | 18.00 | 18.00 | 2.37 | 7.09 | 69.9 | ||
| Max . Permissible pressure: 31.03 bar(450psi) / -10°C~+150°C , 20.67 bar(300psi) /-30°C~-10°C | |||||||||
Vertical accumulators use a U-tube or tube within a tube design to draw gaseous refrigerant off the top of the vessel. At the bottom of the U-tube, an orifice picks up a small amount of oil and liquid refrigerant. The small amount of liquid refrigerant will boil off in the suction line. The oil will be carried with the gaseous refrigerant back to the compressor.
Horizontal accumulators should not be used when the temperature of the liquid refrigerant is less than 15°F (9°C) in the accumulator. At temperature below this point, the oil will become thick and will not draw up the dip tube to be metered back to the compressor.
Selection of a refrigerant accumulator should be made on the basis
of the following 3 capabilities. 1) The accumulator should have an
adequate liquid holding capacity, normally it should not be less
than 50% of the system charge. 2) The accumulator should perform
without adding excessive pressure drop to the system. 3) It should
have the ability of returning liquid at the proper rate and under a
range of load condition.
Install the vertical accumulator as close to the compressor as
possible. And install the horizontal accumulator with the top of
inlet being level so that the return tube is at the lowest part of
the accumulator, leaving a small pool of liquid in the bottom of
the accumulator. Please connect the discharge line from the
evaporator to the inlet of the accumulator and connect the outlet
of the accumulator to the suction line of the compressor.

Model Number Dimensions(inches) In Tube Length (inches) Out Tube Length (inches) Volume () A B C D NPT SCR-06 6.50 21.00 4.00 7.87 1/4 3/4 3/4 9.80 ...
Model No. Dimensions (inches) In Tube Length Out Tube Length Volume () Dia. A Shell B Length CR-101-2 3.35 7.87 3/8 1/4 0.95 CR-101-3 3.35 7.87 3/8 3...
Model Numer Dimensions(inches) Inlet / Outlet I.D. Volume () DIA. A B C D E F Inlet ODS Outlet ODS FPT SHR-2528 5.50 27.98 4.53 13.78 5.37 6.54 1/2 1...
Refrigerant accumulators are applicable to jumbo machine sets, water accessory set or the special designed. The usage is the same as average vertical ...
MODEL NO. Size Conn Dia A SHEEL B LENGTH SHEEL C LENGTH Volume () D RA-S05 5/8" 3.15 10.24 1.37 1.28 1.38 RA-S06 3/4" 12.2 1.37 1.50 1.38 RA-204 1/2" ...
MODEL NO. Size Conn Dia A SHEEL B LENGTH SHEEL C LENGTH Volume () D RA-S05 5/8" 3.15 10.24 1.37 1.28 1.38 RA-S06 3/4" 12.2 1.37 1.50 1.38 RA-204 1/2" ...