Categories | no PD test transformer |
---|---|
Place of Origin: | china |
Brand Name: | CNHV |
Model Number: | HVJFD-2A |
MOQ: | 1 |
The failure testing and positioning of operating the medium and
large sized transformers have always been the points that
electrical engineers focus for a long time. The HRJFD-2A system,
manufactured in the large-sized transformer local discharge
ultrasonic position method and equipment research subject which is
one of the national key scientific and technological project has
provided an effective solution.
The HRJFD-2A system has carried the ultrasonic measurement to the
local discharge of the hundreds of transformers and reactor in
Gezhou Dam 500kV switch station, Wuhan Phoenix Mountain 500kV
transformer substation, Shengyang transformer factory, Hefei
transformer factory, Hengyang transformer factory, Guangzhou power
supply bureau, Hunan electricity generating board, Chongqing
transformers factory and Wuhan steel. This system has the advantage
of operation reliable and easy to operate. It can meet the needs of
measurement. As one of the key items of the of eight-five project,
this electrical device has been widely used for the spot test and
research in the related unit in the north, east, central and
northwest parts of China.
The HRJFD-2A ultrasonic positioning system which is including the
high performance computer, high-sensitivity local discharge sound
probe, programmed amplified filter, high-speed A/D transducer,
transient waveform recording, signal analysis and fault location
software is applied for acquiring, measuring, analyzing,
positioning and spot observing the local discharge ultrasonic
signal in the large-sized transformer, oil-immersed high voltage
electrical apparatus and the GIS electrical operation equipment.
The HRJFD-2A ultrasonic positioning system can position the fault
and the error is less than 250mm. The whole measuring system can
find out the local discharge ultrasonic signal which is less than
1000pC.
Functions and characteristics:
(1) Making the detecting operation of local discharge ultrasonic
more convenient and the analyzing more simple under the platform of
the windows.
(2) Making the signal acquired more reliably for the ultrasonic
sensor has the performance of low noise, high-sensitivity and
anti-jamming.
(3) Making the spot testing more flexible with the local discharge
ultrasonic signal electrical-acoustical position and
acoustical-acoustical position functions
(4) Making the result of the position more precisely by choosing
freely the spherical position calculation and the hyperboloid
position calculation of the ultrasonic signal.
(5) Showing the position coordinates by ultrasonic probe and the
locating point by solid geometric drawing.
(6) Convenient for building the measuring and positioning database
for further analyzing and managing.
(7) Be the local discharge on-line detecting instrument which is
useful for detecting the local generating and developing.
Technical parameter:
The sensitivity of the ultrasonic probe: -150dB
A/D conversion accuracy: 8bit±1/2LSB
Sample length: 32k/channel
Minimum detectable discharge:<50pC (laboratory)<300(1000)pC (spot)
Minimum positional error:<50mm(laboratory)< 250mm (spot)
![]() |